H05V-K Flexible PVC Wire

Fine-stranded H05V-K simplifies protected internal wiring where tight routing and repeated terminations demand flexibility.

Typical Scenarios
Key Specifications
  • Control-panel internal wiring
  • Electrical equipment connections
  • Protected conduit runs
  • Low-voltage cabinet assemblies

 

  • Rated voltage: 300/500 V
  • Conductor: Class 5 flexible copper
  • Insulation: PVC
  • Maximum conductor temperature: +70°C
  • Design standard: EN 50525-2-31

 

Select cable specifications:
Certifications & complance:

Product Highlights

Dense Panel Wiring

Compact control cabinets place terminals, relays and protective devices close together, leaving little room for rigid conductors. H05V-K uses a Class 5 flexible copper conductor that can be dressed through short bends and narrow wiring ducts with less force. This makes it well suited to equipment and panel wiring where neat routing and easy repositioning during assembly matter more than the stiffness of a solid conductor.

Faster Termination

Panel building can involve hundreds of short point-to-point connections. Fine-stranded H05V-K is easy to position at terminal blocks and devices, reducing the time spent forcing a conductor into alignment. Used with terminals and ferrules suitable for Class 5 copper, it supports consistent preparation and clean connections across repetitive cabinet work.

Clear Circuit Identification

H05V-K is commonly used in panels where multiple circuit functions share the same wiring space. A consistent colour scheme helps technicians distinguish power, control and auxiliary conductors during assembly, testing and maintenance. Combined with ferrules and wire numbers, colour identification reduces tracing time and lowers the chance of cross-connection in dense equipment wiring.

Application Areas

Designed for Control cabinets, Distribution panels, Electrical equipment and Protected conduits.

 

Control cabinets

Distribution panels

Electrical equipment

Protected conduits

Technical Data

FAQ

Recommend

GENERAL DATA
  • PVC single-core wire according to DIN VDE 0285-525-2-31 / DIN EN 50525-2-31 and IEC 60227-3
  • Nominal voltage: AC U₀/U 300/500 V
  • Test voltage: 2000 V
  • Temperature range: +5°C to +70°C during installation/flexing; -30°C to +80°C when fixed
  • Maximum conductor operating temperature: +70°C
  • Minimum bending radius, fixed installation: 4 × overall diameter

 

CABLE STRUCTURE
  • Bare copper conductor, finely stranded according to DIN VDE 0295 Class 5 / IEC 60228 Class 5
  • Insulation: PVC compound type TI1 according to DIN EN 50363-3

 

TESTS
  • Conductor construction and resistance according to EN / IEC 60228
  • Flame propagation according to DIN EN / IEC 60332-1-2
  • Voltage and insulation-resistance tests according to the applicable EN 50525 / EN 50395 test programme
  • PVC mechanical and thermal tests according to the applicable EN / IEC 60811 series

 

 

DIMENSIONS

 

Nominal size mm² Insulation mm Nominal OD mm Approx. weight kg/km
1 × 0.5 0.6 2.20 9.1
1 × 0.75 0.6 2.40 11.7
1 × 1 0.6 2.55 14.4

Dimensions are nominal and may vary within the applicable product tolerance.