H1Z2Z2-K Nylon-Barrier Rodent-Resistant Solar Cable
H1Z2Z2-K 1.5 kV DC solar cable with a nylon barrier beneath the outer sheath for PV routes that need a non-metallic physical defence against rodent damage.
hot search
N2XH provides XLPE-insulated, halogen-free power distribution where smoke, corrosive gases and evacuation conditions matter.
Occupied buildings, data facilities and indoor energy plants place greater importance on smoke and corrosive gas behaviour during a fire. N2XH combines XLPE insulation with a low-smoke, halogen-free outer sheath for fixed 0.6/1 kV distribution. This makes it a strong fit for feeders that pass through spaces where reducing smoke density and corrosive combustion products is part of the cable-selection strategy.
N2XH provides a copper-conductor option for inverter AC output, switchboards and fixed building feeders where a halogen-free sheath is required. The copper conductor keeps termination geometry compact, while XLPE insulation supports demanding fixed power distribution. It is particularly useful when the project wants conventional copper termination practice together with improved fire behaviour in the installed cable system.
N2XH-J includes a green/yellow protective conductor, while N2XH-O does not. Selecting the correct construction at design stage keeps the core arrangement, gland size and terminal space aligned with the circuit’s earthing strategy. This is especially important in crowded plant rooms and distribution boards where changing the protective-conductor arrangement late in the project can affect both cable sizing and equipment entries.
Designed for PV inverter AC output, Commercial buildings, Indoor distribution routes and Industrial power systems.
| Configuration | Outer diameter approx. mm | Approx. cable weight kg/km |
|---|---|---|
| 1 × 1.5 | 6.0 | 41 |
| 1 × 2.5 | 6.5 | 53 |
| 1 × 4 | 8.0 | 68 |
| 1 × 6 | 9.0 | 90 |
| 1 × 10 | 9.0 | 140 |
| 1 × 16 | 10.0 | 190 |
| 1 × 25 | 11.0 | 290 |
| 1 × 35 | 12.0 | 390 |
| 1 × 50 | 15.0 | 510 |
| 1 × 70 | 17.0 | 710 |
| 1 × 95 | 19.0 | 960 |
| 1 × 120 | 21.0 | 1200 |
| 1 × 150 | 23.0 | 1480 |
| 1 × 185 | 25.0 | 1910 |
| 1 × 240 | 28.0 | 2370 |
| 1 × 300 | 30.0 | 2970 |
| 1 × 400 | 32.9 | 3957 |
| 2 × 1.5 | 12.0 | 185 |
| 2 × 2.5 | 12.2 | 220 |
| 2 × 4 | 13.2 | 275 |
| 2 × 6 | 14.1 | 335 |
| 2 × 10 | 16.2 | 450 |
| 2 × 16 | 17.8 | 620 |
| 2 × 25 | 21.0 | 930 |
| 3 × 1.5 | 13.0 | 220 |
| 3 × 2.5 | 14.0 | 280 |
| 3 × 4 | 15.0 | 350 |
| 3 × 6 | 16.0 | 420 |
| 3 × 10 | 18.0 | 600 |
| 3 × 16 | 20.0 | 770 |
| 3 × 25 | 21.8 | 1120 |
| 3 × 35 | 24.9 | 1550 |
| 3 × 50 | 25.2 | 1750 |
| 3 × 70 | 29.2 | 2450 |
| 3 × 95 | 32.0 | 3250 |
| 3 × 120 | 34.9 | 4000 |
| 3 × 150 | 39.2 | 5000 |
| 3 × 185 | 44.1 | 6150 |
| 3 × 240 | 49.2 | 8000 |
| 4 × 1.5 | 13.0 | 235 |
| 4 × 2.5 | 14.0 | 290 |
| 4 × 4 | 15.0 | 370 |
| 4 × 6 | 16.0 | 470 |
| 4 × 10 | 18.0 | 670 |
| 4 × 16 | 20.0 | 930 |
| 4 × 25 | 25.0 | 1440 |
| 4 × 35 | 27.0 | 1890 |
| 4 × 50 | 28.0 | 2300 |
| 4 × 70 | 32.0 | 3200 |
| 4 × 95 | 36.0 | 4250 |
| 4 × 120 | 40.2 | 5350 |
| 4 × 150 | 45.8 | 6550 |
| 4 × 185 | 49.5 | 8100 |
| 4 × 240 | 56.0 | 10550 |
| 5 × 1.5 | 14.5 | 280 |
| 5 × 2.5 | 16.0 | 350 |
| 5 × 4 | 17.0 | 450 |
| 5 × 6 | 18.5 | 600 |
| 5 × 10 | 21.0 | 850 |
| 5 × 16 | 24.0 | 1200 |
| 5 × 25 | 28.0 | 1539 |
Dimensions vary by core count and conductor size; use the exact selected construction for gland and termination sizing.
Download TDS
No. They can share the same 0.6/1 kV voltage class, but their insulation, sheath materials, fire behaviour and intended installation conditions differ. The required cable should follow the route and fire specification rather than the voltage rating alone.
Yes, this can be reviewed, but aluminium is not normally a size-for-size replacement for copper. Current, route length, voltage drop, installation method, available space and the equipment termination system all need to be checked before an alternative size is proposed.
Yes. Send the exact cable designation and, where possible, the existing datasheet or project specification. We compare conductor material, construction, voltage rating, standards and the requirements that affect the installation before confirming whether an equivalent can be offered.
Send the exact requirement. The website does not represent every possible production combination. We will check whether the construction can be supplied and whether the required standards or certification scope also cover that version before it is quoted.
Flexible halogen-free AC charging cable for electric and plug-in hybrid vehicles.
Robust 0.6/1 kV copper cable for economical fixed power distribution indoors, outdoors and underground.
Copper XLPE 0.6/1 kV cable for demanding fixed feeders, outdoor routes and power distribution.
Aluminium halogen-free 0.6/1 kV cable for fire-conscious fixed distribution and long feeders.