H07V-K Grounding Cable for Residential PV Systems

Flexible PVC insulated earthing cable for residential solar PV system grounding

Typical Scenarios
Key Specifications
  • PV system grounding and earthing conductor
  • Solar panel frame and mounting structure earthing
  • Protection cable for residential photovoltaic installations
  • DC system protective earth wiring
  • Control cabinet and distribution block earthing
  • Conductor: Class 5 flexible copper according to IEC 60228 / EN 60228
  • Insulation: PVC compound, flame retardant
  • Voltage Rating: 450/750 V nominal
  • Temperature Range: -40°C to +70°C (operating)
  • Rated Test Voltage: Up to 2500 V AC
  • Color: Green/Yellow (standard earthing conductor)
Select cable specifications:
Certifications & complance:

Product Highlights

Installation Environment

H07V-K earthing cable is a flexible single-core conductor used in residential photovoltaic systems for protective earth and grounding connections. The cable is suitable for fixed wiring inside distribution boxes, switch panels, and where a dedicated earth conductor is required for PV mounting structures and protective devices.

Performance & Durability

The cable’s PVC insulation provides resistance to environmental influences, mechanical stress, and abrasion, making it suitable for typical electrical housing installations associated with solar PV systems. Its flexibility allows easy routing through cable ducts and conduits. While primarily designed for indoor or protected installation, the insulation offers some resistance to moisture and weather when routed appropriately.

Compliance & Safety

H07V-K complies with EN50525 standards for PVC insulated flexible conductors. It is flame retardant and meets RoHS and REACH environmental compliance requirements. The cable’s green/yellow insulation ensures clear earth identification and conforms to safety colorcoding standards.

Application Areas

Designed to serve as the protective earth conductor within residential PV systems, H07VK cable ensures safe grounding continuity between PV module frames, mounting structures, and electrical distribution earth paths.

Compatible with earthing bars and ground terminals in PV combiner boxes

Suitable for connection to solar panel frame earth points

Used in conjunction with PV inverter earth grounding points

Can integrate into residential switchboard and distribution earth networks

Technical Data

FAQ

Recommend

CABLE STRUCTURE
  • Bare copper,annealed stranded acc.to EN60228/IEC60228 Class 5
  • Insulation:PVC(TI 1)acc.to EN50363-3

 

TESTS
  • Conductor resistance acc.to EN60228/IEC60228
  • Mechanical tests before and after ageing acc.to EN60811 1-1&1-2
  • Loss of mass acc.to EN60811-3-2 8.1
  • Pressure test at high temperature acc.to EN60811-3-1 8.1
  • Heat shock acc.to EN60811-3-1 9.1
  • Bending test at low temperature acc.to EN60811-1-4 8.1
  • Elongation test at low temperature acc.to EN60811-1-4 8.3
  • Voltage test on completed cable acc.to EN50395 Clause 6
  • Insulation resistance acc.to EN50395 8.1
  • Spark test acc.to EN50395 10.2
  • Long term resistance of insulation to d.c.acc.to EN50395 Clause 9

 

 

Description Nominal cross section mm² OD of conductor mm Thickness of insulation mm Diameter of cable mm Approx. weight kg/km Cable Color
HO7V-K 15 1.6 0.7 3.0 19.5
HO7V-K 2.5 2.0 0.8 3.6 30.5
HO7V-K 4 2.5 0.8 4.1 43.5
HO7V-K 6 3.1 0.8 4.7 62
HO7V-K 10 4.1 1.0 6.1 106
HO7V-K 16 5.5 1.0 7.5 160
HO7V-K 25 6.7 1.2 9.1 246
HO7V-K 35 8.2 1.2 10.6 339
HO7V-K 50 10.0 1.4 12.8 483
HO7V-K 70 11.6 1.4 14.4 668
HO7V-K 95 13.0 1.6 16.2 877
HO7V-K 120 14.4 1.6 17.6 1136

Download TDS

Can you check an equivalent cable from another manufacturer?

Yes. Send the exact cable designation and, where possible, the existing datasheet or project specification. We compare conductor material, construction, voltage rating, standards and the requirements that affect the installation before confirming whether an equivalent can be offered.

What if the required size, core count or construction is not shown on the website?

Send the exact requirement. The website does not represent every possible production combination. We will check whether the construction can be supplied and whether the required standards or certification scope also cover that version before it is quoted.

Can LV and MV cables be supplied in the drum lengths shown in our cable schedule?

Requested drum lengths can be reviewed with the cable schedule. What is practical depends on cable dimensions and weight, total quantity, drum capacity and transport or site-handling limits, so the required lengths should be included with the enquiry.

Is there one MOQ for all HORNOUR cable products?

No single MOQ applies across the entire range. The practical quantity depends on the cable type, size, construction, packing and production conditions. Send the actual cable list and quantities and we can confirm the applicable requirement for those items.