Please fill out the form below to obtain the download document(s) you need
Notice: By submitting this form. you confirm that you have read and accepted our Privacy Policy (link toPrivacy Policy). We will contact you within 24 hours of receiving your request.

EN

LME Metal Price
Metal Exchange Prices
Metal Rate
Copper € 1,261.52 / 100kg
Copper (MK) € 1,389.12 / 100kg
MS58 € 1,074.00 / 100kg
Al € 412.52 / 100kg
Ni € 1,571.63 / 100kg
Ag € 2,046.80 / 1,000g
Gold € 116,900.00 / 1,000g
Quotes as of: 15.09.2026
All information is provided without guarantee or liability.

Not sure which cable to choose?
Explore Cable Selection Guide

Request Engineering Support

NA2XS(F)2Y Medium-Voltage Power Cable – 20.8-36 kV

High-performance medium-voltage cable for demanding industrial and commercial networks

Typical Scenarios
  • Industrial and commercial power distribution (HDPE for UV-exposed installations, MDPE for underground).
  • Connection between transformer stations, medium-voltage switchgear, and distribution panels.
  • Conduits or direct-buried routing requiring mechanical and electrical protection.
  • Applications demanding long-term reliability under UV, moisture, and mechanical stress.
Certifications & complance:

Product Highlights

Installation Environment

Ideal for high-demand industrial and commercial energy distribution, suitable for direct burial, conduit, or exposed routing. Sheath options: HDPE for UV-exposed areas, MDPE for underground.

Performance & Durability

XLPE insulation and metallic sheath offer high dielectric and mechanical strength. Resistant to moisture, UV, and physical stress for reliable long-term operation.

XLPE insulation and metallic sheath offer high dielectric and mechanical strength. Resistant to moisture, UV, and physical stress for reliable long-term operation.

Certified CE, RoHS, REACH. Meets international medium-voltage standards to ensure safety and regulatory compliance.

Application Areas

Compatible with industrial and commercial switchgear, transformers, and medium-voltage accessories rated 18-30 kV.

Supports joints and terminations rated for 18-30 kV medium-voltage networks.

Technical Data

FAQ

Recommend

CABLE STRUCTURE
  • Aluminium,annealed stranded acc.to DIN VDE 0295 Class 2/IEC60228 Class 2
  • Conductor Screen:Semi-conductive material (bonded)
  • Insulation:Cross-Linked Polyethylene (XLPE)
  • Insulation Screen:Sem-conductive material (bonded)
  • Screen:Copper wires and copper tape
  • Outer sheath:MDPE
TESTS
  • Conductor construction and resistance acc.to IEC 60228
  • Partial discharge test acc.to IEC 60885-3
  • Hot set test acc.to lEC60811-507
  • Impulse test acc.to IEC60230
  • Ageing properties acc.to IEC60811-501 IEC60811-401
  • Loss of mass test acc.to IEC60811-409
  • Pressure test at high temperature acc.to IEC60811-508
  • Low temperature test acc.to IEC60811-504 IEC60811-505&1EC60811-506
  • Heat shock test acc.to IEC60811-509
  • Water absorption test acc.to IEC60811-402
  • WShrinkage test for XLPE insulation acc.to IEC60811-502
  • Water penetration test acc.to IEC60502-2 Annex F and Annex H



Description Cross Section
m㎡
OD of conductor mm Thickness of Semi- con . layer Inner mm Thickness of Semi- con . layer Outer mm Thickness of Insulation mm Wire Screen cross section m㎡ Tape Screen Diameter mm Thickness of Sheath mm Cable overall diameter mm Cable weight kg/km
NA2XS(F)2Y 18/30(36)kV 1 x 50 8.1 0.7 0.7 8 16 1 x 0.1 x 10 2 33 1000
NA2XS(F)2Y 18/30(36)kV 1 x 70 9.7 0.7 0.7 8 16 1 x 0.1 x 10 2 35 1100
NA2XS(F)2Y 18/30(36)kV 1 x 95 11.4 0.7 0.7 8 16 1 x 0.1 x 10 2.1 37 1300
NA2XS(F)2Y 18/30(36)kV 1 x 120 12.7 0.7 0.7 8 16 1 x 0.1 x 10 2.1 38 1400
NA2XS(F)2Y 18/30(36)kV 1 x 150 14.5 0.7 0.7 8 25 1 x 0.1 x 10 2.2 40 1600
NA2XS(F)2Y 18/30(36)kV 1 x 185 15.9 0.7 0.7 8 25 1 x 0.1 x 10 2.2 42 1800
NA2XS(F)2Y 18/30(36)kV 1 x 240 18.6 0.7 0.7 8 25 1 x 0.1 x 10 2.3 44 2000
NA2XS(F)2Y 18/30(36)kV 1 x 300 20.7 0.7 0.7 8 25 1 x 0.1 x 10 2.4 47 2250
NA2XS(F)2Y 18/30(36)kV 1 x 400 23.5 0.7 0.7 8 35 1 x 0.1 x 10 2.5 50 2750
NA2XS(F)2Y 18/30(36)kV 1 x 500 26.5 0.7 0.7 8 35 1 x 0.1 x 10 2.6 53 3250
NA2XS(F)2Y 18/30(36)kV 1 x 630 30.2 0.7 0.7 8 35 1 x 0.1 x 10 2.7 57 3750
NA2XS(F)2Y 18/30(36)kV 1 x 800 34.2 0.7 0.7 8 35 1 x 0.1 x 10 2.9 61 4400

Download TDS

Can you check an equivalent cable from another manufacturer?

Yes. Send the exact cable designation and, where possible, the existing datasheet or project specification. We compare conductor material, construction, voltage rating, standards and the requirements that affect the installation before confirming whether an equivalent can be offered.

What if the required size, core count or construction is not shown on the website?

Send the exact requirement. The website does not represent every possible production combination. We will check whether the construction can be supplied and whether the required standards or certification scope also cover that version before it is quoted.

Can LV and MV cables be supplied in the drum lengths shown in our cable schedule?

Requested drum lengths can be reviewed with the cable schedule. What is practical depends on cable dimensions and weight, total quantity, drum capacity and transport or site-handling limits, so the required lengths should be included with the enquiry.

Is there one MOQ for all HORNOUR cable products?

No single MOQ applies across the entire range. The practical quantity depends on the cable type, size, construction, packing and production conditions. Send the actual cable list and quantities and we can confirm the applicable requirement for those items.